Truly Green Products

Blog

Common overlay image

Cooling Tower Efficiency: How to Calculate and Improve It

Cooling Tower Efficiency guide graphic with a gray industrial cooling tower, pipes, sensors, and temperature gauges on a white background.

To calculate cooling tower efficiency, measure three temperatures at the same time: the hot water entering the tower, the cold water leaving it, and the wet-bulb temperature of the intake air. Then apply Efficiency (%) = Range ÷ (Range + Approach) × 100, where range is hot minus cold and approach is cold minus wet-bulb. Well-maintained towers commonly land between 60% and 80%, and a steady drop at similar conditions signals lost capacity.

The trouble is that the number only helps if the readings are right and you know what to compare it with. Many operators grab a dry-bulb reading, log temperatures while the load swings, or hold one fixed benchmark against a tower designed for a different approach. The result is a percentage that sends maintenance in the wrong direction, or nowhere at all.

This guide walks through the job in four steps: measure, calculate, benchmark, and diagnose. It starts with what the terms mean. Eco Safeway supplies descalers for cooling towers, chillers and heat exchangers, so the last step also covers scale, one of the most common water-side causes of lost performance.

What cooling tower efficiency measures

Cooling tower efficiency is the share of the cooling that the weather allows that your tower actually delivers. The weather sets a hard floor, because an evaporative tower can never cool water below the wet-bulb temperature of the air entering it. You will also see this calculation called cooling tower effectiveness. It is the same math.

How the tower removes heat

Warm water from your chiller or process loop is sprayed over fill media while a fan moves air through it. A small portion of the water evaporates, and that evaporation carries the heat out of the system. The rest falls into the basin and returns to the load.

Cutaway of a cooling tower showing nozzles, fill media, a fan and a basin.

Because evaporation does the work, humid air limits a tower more than hot, dry air does. This working principle sits behind every figure in the steps below.

The temperatures and terms you need

Three temperatures and two calculated values drive the whole calculation.

Term What it is Where you get it
Hot water temperature Water entering the tower Return line or inlet header
Cold water temperature Water leaving the tower Basin outlet or supply line
Wet-bulb temperature Lowest temperature evaporation can reach Air intake of the tower
Range Hot water minus cold water Calculated
Approach Cold water minus wet-bulb Calculated

Range shows how much temperature drop the tower delivers. Approach shows how close the cold water gets to the wet-bulb limit, and a smaller approach means a better-performing tower. Because range plus approach equals hot water minus wet-bulb, the formula expresses the drop you capture as a share of the total drop available.

Efficiency is the share of the cooling the wet-bulb temperature allows that your tower actually delivers.

Step 1. Measure three temperatures

Record hot water, cold water and wet-bulb temperature at the same moment, while the tower runs at a steady load. Readings taken during a load swing or a chiller staging change do not describe the tower.

Read the water temperatures

Take the hot water temperature at the return line or inlet header where water enters the tower. Take the cold water temperature at the basin outlet or the supply line leaving the basin. Use calibrated probes or thermowell sensors, and keep the cold water probe away from the make-up water inlet, which can skew the reading. Note the circulating flow in GPM as well, because you need it in step 2.

Read the wet-bulb temperature

Measure wet-bulb at the tower's air intake with a sling or aspirating psychrometer. An on-site weather station or a control-system sensor also works. Never substitute dry-bulb temperature, and treat a regional weather report with caution, because it can differ from the air your tower actually draws in.

Sling psychrometer hanging at a cooling tower air intake next to a pipe sensor.

Use this checklist before you log a set of readings:

  • Take all three temperatures at the same time.
  • Confirm that load and flow are steady.
  • Check that instruments are calibrated.
  • Record date, time, flow and the location of the wet-bulb reading.

A wrong wet-bulb reading ruins the whole calculation, so measure it at the tower intake, not from a weather app.

Step 2. Calculate range, approach and efficiency

Subtract to get range and approach, then divide range by the sum of the two and multiply by 100. The math takes under a minute once the readings are trustworthy.

Work one example through

Use a common rating point of 95°F hot water, 85°F cold water and 78°F wet-bulb:

  • Range = 95 − 85 = 10°F
  • Approach = 85 − 78 = 7°F
  • Efficiency = 10 ÷ (10 + 7) × 100 = 58.8%

That result sits just under the 60% mark that some references treat as a warning level. Yet many towers are rated at exactly this point, so 58.8% can be a healthy tower. Step 3 explains why design conditions matter more than a fixed cutoff.

To run this as a calculator, put hot water in cell B1, cold water in B2 and wet-bulb in B3 of a spreadsheet, then paste these formulas:

Range      = B1 - B2
Approach   = B2 - B3
Efficiency = (B1 - B2) / (B1 - B3) * 100

Cross-check with heat rejection and water loss

Efficiency does not tell you how much heat the tower rejects. For that, use Heat Rejection (BTU/hr) = flow (GPM) × range (°F) × 500, then divide by 12,000 to get tons. At 1,000 GPM and a 10°F range, that is 5,000,000 BTU/hr, or about 417 tons.

Evaporation loss follows from the same range. The standard estimate is 0.00085 × flow × range in °F. The 0.00085 is an empirical factor, and the metric version writes it as 0.00085 × 1.8 × flow × range in °C. At 1,000 GPM and 10°F, you lose about 8.5 GPM, or 0.85% of the flow, to evaporation.

Pair efficiency with range and flow, so you can tell whether the load changed or the tower did.

Step 3. Compare your result with typical values

Most references put a healthy tower between 60% and 80%, with 70% to 75% often quoted as common. Treat these as guide rails, not pass-fail lines.

Typical efficiency values

Efficiency How to read it
Above 80% Excellent. Double-check your wet-bulb reading.
70% to 80% Normal for a well-maintained tower.
60% to 70% Acceptable. Compare against your design point.
Below 60% Investigate, unless your design point is lower.

Ladder of four cooling tower efficiency bands, from below 60% to above 80%.

Judge your result against design and trend

Your tower's own design approach is the fairest benchmark. A tower designed for a 7°F approach that now runs at 12°F has lost capacity, whatever the percentage says. Pull the design range, approach and wet-bulb from the manufacturer's data and compare.

Then build a trend log. Efficiency moves with load and wet-bulb, so compare readings taken at similar conditions, monthly if you can. A steady downward drift at comparable load is the signal to act on, and a single low day in humid weather usually is not.

The trend at comparable conditions tells you more than any single reading against a fixed benchmark.

Step 4. Find what is costing you efficiency

Most losses trace back to fill, water distribution, airflow, recirculation or water chemistry. Start with the symptom, then inspect the matching component.

Match the symptom to the cause

Cause What you will see What to check
Fouled or broken fill Rising approach, uneven water film Inspect, clean or replace fill
Clogged nozzles or basins Dry spots on fill, uneven spray Nozzles and distribution basins
Weak airflow Higher approach at normal load Fan pitch, belts, drive, blocked louvers
Air recirculation Intake wet-bulb above ambient, worse on windy days Placement, discharge, nearby structures
Scale and biological growth Deposits on fill and basin Cycles of concentration, treatment program

Recirculation deserves extra attention. When warm, moist exhaust air re-enters the intake, the effective wet-bulb rises, so approach grows even though the tower itself has not changed. Verify it by measuring wet-bulb at the intake and comparing it with ambient.

Scale, blowdown and water chemistry

Water leaves a tower through evaporation, drift and blowdown, and dissolved solids stay behind as water evaporates. Left unmanaged, those solids form scale on fill and heat transfer surfaces, which restricts water flow and cuts performance. This is the main downside of towers: they use water continuously and need treatment to control scale and bacteria such as Legionella.

The U.S. Department of Energy notes that raising cycles of concentration from three to six cuts make-up water by 20% and blowdown by 50%, within the limits of your water chemistry. See its cooling tower management guidance. Work with your water treatment specialist on the right limit, because higher cycles also raise the scale risk.

Clean, adjust, then replace: fix the cheapest cause that matches your symptoms before you spend on hardware.

Putting the numbers to work

Cooling tower efficiency comes down to three clean readings and one formula. Compare the result with your design point, log it monthly, and diagnose by symptom when it drifts. If scale is the cause, descale following your equipment manufacturer's requirements and your water treatment specialist's guidance.

For mineral scale in towers, chillers and heat exchangers, Eco Safeway's Cooling Tower Descaler is a non-corrosive, CIP-compatible option sold from 1 gallon to 275-gallon totes. Confirm your equipment, deposit type and required volume before you order.

Back Next

Leave a comment

Please note, comments need to be approved before they are published.